Reference

Copper Busbar Weight and Current Calculator

Enter the section and length, get the weight per piece and per metre, plus an indicative current capacity for the same section. The weight is pure geometry from copper density; the current figure is a planning estimate, not a substitute for the thermal test.

Copper Busbar Weight and Current Calculator
Geometry only — a planning number, not a thermal rating.

Calculate section, weight and current

Enter the bar section and length. The result uses pure geometry and a 1.5 A/mm² planning current — not a thermal test.

Section250 mm²
Weight2.24 kg/m
Total weight2.24 kg
Indicative current375 A

Indicative only. It does not model skin effect, temperature rise, bundling or joint resistance. For a certified current, send the drawing and the test condition.

At a glance

  • All design guides — Tolerances, materials and finishing, one library.

Common busbar sizes, weight per metre

Above roughly 1000 A the section stops being the limiting factor – joint quality, plating and how the bar is supported start to decide the temperature rise. That is why we quote the joint face separately from the plate.

Thickness × widthSection (mm²)Weight (kg/m)Indicative current (1.5 A/mm²)
3 × 20 mm600.5490 A
3 × 25 mm750.67113 A
5 × 30 mm1501.34225 A
5 × 40 mm2001.79300 A
5 × 50 mm2502.24375 A
10 × 60 mm6005.38900 A
10 × 80 mm8007.171200 A
10 × 100 mm10008.961500 A

What the number does not tell you

  • Temperature rise. A bar that is fine at 30 K rise can fail at 50 K, and the allowable rise comes from your enclosure and the standard you are certified to.
  • Joints. Plating thickness, contact area and bolt torque decide joint temperature more than the plate section does.
  • Bundling. Bars stacked with small gaps run hotter than the same section in free air.
  • Skin effect. At high frequency the effective section drops; above a few hundred Hz use a laminated or profiled bar rather than a thicker one.

Related

  • Copper busbar design guide — Thickness versus current, C11000 or C18150, plating and masking, and why the joint face is a flatness requirement.
  • Copper busbar part family — Sizes, tolerances and finishes we quote most often, with the joint area plated and the rest masked.

Send the drawing and the current

State the continuous current, the allowable temperature rise and the joint plating – you get a DFM review and a price within one business day on weekdays.

Send drawings. Get a reviewed quote.

One business day response, engineering comments included. No account needed.

MOQ from prototype to seriesNDA on requestlesley@livoelectrical.com